Abstract
This paper investigates DC network partition and alternative DC fault protection strategy for Multi-terminal HVDC (MTDC) system. Fast acting DC Circuit Breakers (DCCBs) or fault blocking DC-DC converters can be configured at strategic locations to allow the entire MTDC system to be operated interconnected but partitioned into islanded DC network zones following faults. In case of any DC fault event, the DCCBs or DC-DC converters at the strategic cable connections that link the different DC network partitions are opened or blocked such that the faulty DC network zone is quickly isolated from the remaining of the MTDC system. Thus, the healthy DC network zone can remain operational or recover quickly to restore power transmission. Each DC zone can be protected using AC circuit breakers and DC switches for cost reduction. The validity of the proposed protection strategy is confirmed using MATLAB/SIMULINK simulations
Original language | English |
---|---|
Title of host publication | 2016 Power and Energy Society General Meeting (PESGM) |
Place of Publication | Piscataway, NJ. |
Publisher | IEEE |
Number of pages | 5 |
ISBN (Print) | 978-1-5090-4168-8 |
DOIs | |
Publication status | Published - 14 Nov 2016 |
Event | IEEE PES General Meeting 2016 - Sheraton Boston Hotel, Boston, United States Duration: 17 Jul 2016 → 21 Jul 2016 http://www.pes-gm.org/2016/ |
Conference
Conference | IEEE PES General Meeting 2016 |
---|---|
Country/Territory | United States |
City | Boston |
Period | 17/07/16 → 21/07/16 |
Internet address |
Keywords
- DC fault
- DC network partition
- DC circuit breaker
- multi-terminal HVDC system